Megger MIT1020/2 Insulation Resistance Tester

About this item

Product Description

The Megger MIT 1020-2 insulation resistance tester is designed specifically to assist you with the testing and maintenance of high voltage electrical equipment. IEEE 43-2000 recommends the use of 10 kV for motor windings rated above 12 kV and the Megger MIT 1020/2 facilitates this.

Information displayed includes resistance, voltage, leakage current, capacitance, battery status and time constant. In addition, the elapsed time of the test is displayed constantly removing the need for separate timers.

The Megger MIT 1020-2 can test when being powered by the mains or its internal rechargeable battery, a great benefit when site conditions are unknown or long term testing is required.

To further enhance the flexibility of the instrument it has the facility to set the test voltage in steps from 50 V to the maximum output voltage avoiding the expense of several insulation resistance testers to meet your application needs.

The Megger MIT 1020-2 is a microprocessor controlled 10 kV insulation tester offering measurement capability of up to 35 TΩ. The instrument performs automatic tests and has data storage and data retrieval facilities. Polarization index and dielectric discharge tests are performed automatically, and test duration and voltages can be adjusted according to user preference for these tests. A step voltage test can be performed automatically, with a default voltage of 1 kV, and test duration of 5 minutes. It is possible for the user to set different voltages and test durations for the step voltage test. The MIT1020/2 can be powered from the mains supply or by its own internal rechargeable battery, which provides for at least 4 hours of continuous testing with a 100 MΩ load. A battery level indicator on the LCD display indicates battery capacity. Connecting power to the mains supply connector will automatically charge the battery whether the instrument is switched ‘on’ or ‘off’, except during testing. A high level of internal isolation allows the instrument to be used while the unit is supplied from the mains. An internal battery management system switches the instrument off after ten minutes of inactivity. If the battery approaches a very low state of charge the instrument turns itself off, and mains power must be applied before the instrument can be used again. Recorded test results and settings will not be lost when the instrument is switched off. A comprehensive LCD display shows resistance, current, capacitance, time constant, voltage, timer measurements, and figure of merit measurements such as polarization index.

INCLUDES:
Accessory Bag
Carrying Case
Large Test Lead
Manual
Power Cord
Serial Cable
Small Test Lead
Software
USB Cable

AIN 100038010071016
Starting from $212.00
Rent
From
Duration
Months
Weeks
Days
Quantity Required:

Check Availability

Specifications

Group: Megohmmeters/Ground Resistance Testers/Insulation Testers
Item #: 362
Product model number: MIT1020/2
Location: DENVER
Suggested Kit: 0